Eberry VS1-12 Electrical equipment supplies VCB for switchgear 11KV High Voltage Vacuum Circuit Breaker
NO | Item | Unit | Technical parameters | | | ||
1 | Rated voltage | KV | 12 | | | ||
2 | Rated short-duration power frequency withstand voltage | KV | 42/48(Interphase, ground/fracture) | | | ||
3 | Rated lightning impulse withstand voltage | KV | 42/48(Interphase, ground/fracture) | | | ||
4 | Rated frequency | Hz | 50 | | | ||
5 | Rated current | A | 630 1250 | 630 1250 1600 2000 2500 3150 | 630 1250 1600 2000 2500 3150 | ||
6 | Rated short-circuit breaking current | KA | 20/25 | 31.5 | 40 | ||
7 | Rated short-time withstand voltage | KV | 20/25 | 31.5 | 40 | ||
8 | Rated short circuit duration | S | 4 | | | ||
9 | Rated peak withstand current | KA | 50/63 | 80 | 100 | ||
10 | Rated short circuit closing current | KA | 50/63 | 80 | 100 | ||
11 | Secondary circuit power frequency withstand voltage (1min) | | 2000 | | | ||
12 | Rated single / back to back capacitor group breaking current | A | 630/400(40kA:800/400) | | | ||
13 | Rated capacitor bank closing current | KA | 12.5 (frequency is not greater than) | | | ||
14 | Mechanical life | | 20000 | | | ||
15 | Rated current breaking times (electrical life) | | 20000 | | | ||
16 | Rated short circuit current breaking times | TIMES | 50(40KA≤30) | | | ||
17 | Dynamic and static contacts allow wear cumulative thickness | MM | 3 | | | ||
18 | Energy storage time | S | ≤10 | | | ||
19 | Contact opening distance | MM | 11±1 | | | ||
20 | Overtravel | | 3.5±0.5 | | | ||
21 | Contact closing bounce time | MS | ≤2(40KA≤3) | | | ||
22 | Three-phase split/closed period | | ≤2 | | | ||
23 | Average opening speed (contacts are separated by -8mm) | M/S | 1.2±0.2 | | | ||
24 | Main conductive loop resistance | | 0.6±0.2 | | | ||
25 | Main conductive loop resistance | μΩ | ≤50(630A)≤45(1250A) ≤40 (1600,2000A)≤35 (2500A or more) | | | ||
26 | Rated operation sequence | | 0-0.3s-Co-180s-Co | | |