Add to Cart
Home use 3 pole 32A AC mcb moulded case 3p mccb Mini Circuit Breakers
Table 1 | ||||
| | | Rated short circuit breaking capacity | |
Expected current in the last test line(A) | Power factor | |||
63,80,100,125 | 1,2,3,4 | 230/400 | 4000 | 0.45~0.50 |
Table 2 | ||||
Ambient air humidity | I/In | Expected result in the last test | Start status | |
In≤63A | In>63A | |||
| 1.05 | Not trip within 1 hour | Not trip within 2 hours | Cold status starts |
1.30 | Not trip within 1 hour | Trip within 2 hours | Hot status starts | |
3.0 | Release time>3s | Release time>5s | Hot status starts | |
| 5.0~10.0(C) | Operate within≤0.1s | | |
10.0~14.0(D) | Operate within≤0.1s |